Eaton Power-Sure 800 Line Conditioner - Lightning, AC Surge, Harmonics, AC Noise protection - Hardwired - 208 V AC, 240 V AC, 480 V AC Input - 10 kVA - 10 kW
Eaton Power-Sure 800 Line Conditioner - Lightning, AC Surge, Harmonics, AC Noise protection - Hardwired - 208 V AC, 240 V AC, 480 V AC Input - 10 kVA - 10 kW
Eaton Power-Sure 800 Line Conditioner - Lightning, AC Surge, Harmonics, AC Noise protection - Hardwired - 208 V AC, 240 V AC, 480 V AC Input - 10 kVA - 10 kW
Part Num:
T800F-10000Condition: Brand New$9,143.74
Add To Cart
BUY MORE & SAVE
Need 5 or more of these on a single order?
Ask for a quotation here.
We generally respond within 3 business hours.
Close
Total price is...Every facet of our daily life is being automated by faster microprocessors and microprocessor-based equipment which require steady continuous power. As market pressures force the deregulation of the electrical industry, utility companies have less and less control over the quality of power supplied to sensitive electronic equipment. In industry, the effects of unreliable power can be seen in the erroneous motion of computer-controlled milling machines, causing irreparable damage to expensive manufacturing equipment or finished products. Additionally, poor power quality can cause motor driven equipment to operate inefficiently and overheat, causing premature failure. In data processing and medical applications, the effects of unreliable power can be translated into incorrect data, lost memory, premature component failure, mixed and garbled data and inaccurate diagnostics. Power conditioning alleviates these problems.
General Information
|
Manufacturer | Eaton Corporation |
Manufacturer Part Number | T800F10000 |
Manufacturer Website Address | https://www.eaton.com/EatonCom/Markets/NorthAmerica |
Brand Name | Eaton |
Product Line | Power-Sure |
Product Model | T800F-10000 |
Product Name | Power-Sure 800 Line Conditioner |
Product Type | Line Conditioner |
Technical Information
|
Protection Type | Lightning | AC Surge | Harmonics | AC Noise |
Plug/Connector Type | Hardwired |
Receptacle Type | Hardwired |
Power Description
|
Load Capacity (VA) | 10 kW |
Load Capacity (Watt) | 10 kW |
Input Voltage | 208 V AC | 240 V AC | 480 V AC |
Output Voltage | 240 V AC |
Maximum Frequency | 50 Hz |
Physical Characteristics
|
Height | 28.50" (723.90 mm) |
Width | 23" (584.20 mm) |
Depth | 20" (508 mm) |
Weight (Approximate) | 229.97 kg |
Miscellaneous
|
Additional Information | - Line Regulation: +/- 2% Vout for +10% to -20% Vin at 100% Load
- Load Regulation: +/-3% for 0% to 100% load
- Immunity to Distortion: @40% THD Vin, 5% Max THD Vout
- Ride-through Capability: 1 cycle
- Voltage Recovery: 2 cycles to 95%, 3 cycles to 100%
- K-Factor: K-30 Rated
- Power Factor Correction: Input of 0.95 typical
- Harmonic Attenuation: -23dB for load reflected harmonics
- Galvanic Isolation: NEC 250-5d, 0.001 pf
- Surge Protection: UL 1449 Rating 330v; ANSI/IEEE C62.41-Cat B3
- Common Mode Noise Attenuation: 140 dB
- Transverse Mode Noise Attenuation: 120 dB
- Reliability: 200,000 hours (MTBF)
- Audible Noise: 1 meter A scale, 52dB to 56dB
- Efficiency: Approx. 92% at full load
|
Warranty
|
Limited Warranty | 2 Year |