Total price is...Every facet of our daily life is being automated by faster microprocessors and microprocessor-based equipment which require steady continuous power. As market pressures force the deregulation of the electrical industry, utility companies have less and less control over the quality of power supplied to sensitive electronic equipment. In data processing and medical applications, the effects of unreliable power can be translated into incorrect data, lost memory, premature component failure, mixed and garbled data and inaccurate diagnostics. Power conditioning alleviates these problems. For this reason, the Power-Sure 800 was designed using a special high "K-Factor" transformer capable of handling these harmonics without overheating. The Power-Sure 800 has one of the highest "K-Factors" in the industry. Additionally, the Power-Sure 800 virtually eliminates any transient harmonics being reflected back onto the power lines, thus preventing damage to building wiring.
General Information
|
Manufacturer | Eaton Corporation |
Manufacturer Part Number | T800F05000 |
Manufacturer Website Address | https://www.eaton.com/EatonCom/Markets/NorthAmerica |
Brand Name | Eaton |
Product Line | Power-Sure |
Product Model | T800F-05000 |
Product Name | Power-Sure 800 T800F-05000 Line Conditioner |
Product Type | Line Conditioner |
Technical Information
|
Protection Type | AC Surge | AC Noise | Harmonics |
Physical Characteristics
|
Height | 28.50" (723.90 mm) |
Width | 20" (508 mm) |
Depth | 23" (584.20 mm) |
Weight (Approximate) | 184.61 kg |
Miscellaneous
|
Additional Information | - VA Rating: 5000VA
- Watt Rating: 5000W
- AC 120/208/240/480 V - 5 KW
- Line Regulation: +/- 2% VOut for +10% to -20% V In at 100% Load
- Load Regulation: +/-3% for 0% to 100% load
- Immunity to Distortion: @ 40% THD V In, 5% Max THD VOut
- Ride-through Capability: 1 cycle
- Voltage Recovery: 2 cycles to 95%, 3 cycles to 100%
- K-Factor: K-30 Rated
- Power Factor Correction: Input of 0.95 typical
- Harmonic Attenuation: -23dB for load reflected harmonics
- Galvanic Isolation: NEC 250-5d, 0.001 pf
- Surge Protection: UL 1449 Rating 330 V, ANSI/IEEE 62.41-Cat B3
- Common Mode Noise Attenuation: 140 dB
- Transverse Mode Noise Attenuation: 120 dB
- Reliability: 200,000 hours (MTBF)
- Audible Noise: 52dB to 56dB measured at 1 meter, A Scale
- Efficiency: Approx. 92% at full load
|
Certifications & Standards | Safety: Underwriters Laboratories UL 1012 - UL 544 - cUL |
Country of Origin | United States |
Warranty
|
Limited Warranty | 2 Year |